Insulation monitor relays

 

CURRENT LOCATION:HOME >> PRODUCTS >> Relays >> Insulation monitor relays

Bense KNY-EVS Insulation Monitoring Device dc ground fault detection for DC charging stations for charging of electric vehicles

Interested in this product? SEND ENQUIRY NOW.Your enquiry will be replied within 24 hours.
Product Details

Overview

Bense KNY-EVS insulation Monitor device is suitable for AC and DC ungrounded systems below 1000V. It is often used in electric vehicle charging devices, UPS power supply systems, DC power supply systems in the communication industry, isolated medical power systems, and any AC and DC ungrounded systems.

Features

1. Suitable for AC and DC ungrounded systems below 1000V;

2. Adaptive system distributed capacitance, no need for bus voltage;

3. Measurement accuracy below 100μF is within 5%;

4. A set of digital input, a set of relay alarm output;

5. Optional RS-485 and CAN communication methods;

6. Wide range control power input.

Product Paramenters

Input voltage: DC 9~36V

Normal consumption: about 4VA

Network voltage: DC 0~1000V or AC 0~600V

Alarm value: Default 80 KΩ

Internal AC resistance value: >. 400 KΩ

internal DC resistance value: > 400 KΩ

internal test voltage: +/ -24V

Maximum test current (R=0) < 0.1mA

Measuring accuracy: 5%

Contact: 1 group of independent alarm signal output

maximum power capacity: AC 125V, 2A or DC 30V 2A

operation data Operation mode: continuous operation

operating temperature range: -20... +60℃

pollution level: 11 pulse

group immunity: 4KV IEC/EN 6000-4-4

Control surge voltage between power cables 2KV IEC/EN 6000-4-5

Control surge voltage between power cables and ground 4KV IEC/EN 6000-4-5

Conducted disturbance Anti-disturbance 10Vr.m.s IEC/EN 6000-4-6

Power frequency field immunity 10A/m IEC/EN 6000-4-8

Radiation emission Limit Class B EN 55

Enclosure: IP20 IEC/EN 60 529

Terminals: IP20 IEC/EN 60 529

Wiring: L1, L2: 800V high voltage wire, 2.5 mm2 PE: 2.5mm2 wire

Other terminals: wires larger than 1.5 mm2

Installation: Use M4 screws with a length of 15 mm (recommended)

Weight: about 300g